2008 N.E.C.
Swimming Pool Electrical Codes

Gunther Home Inspections

ELECTRICAL WIRING REQUIREMENTS FOR SWIMMING POOLS
2008 National Electrical Code / 2010 Residential Code of New York State

ALL INGROUND POOLS AND ANY POOL OVER 18' IN DIMENTION THAT IS ABOVE GROUND AND HOLDING WATER GREATER THAN 42" DEEP IS TO BE CONSIDERED A PERMINENTLY INSTALLED POOL

1) Pool Pump Receptacle (Outlet) and Wiring Method

a. If a pump motor receptacle is located between 6’ – 10’ from the inside pool wall, the receptacle must be a single twist-lock outlet, grounded, and Ground Fault Circuit Interrupter (GFCI) protected
b
. Receptacle must have a weatherproof cover that can be closed when the cord is plugged in. (In-use type cover)
c
. The circuit line for the pump motor must be a continuous line going directly to the panel box, and is to be isolated from all other receptacles.
d
. Wire for the pump motor shall not be less than #12 AWG insulated copper grounded wire, and must be in conduit. (except when entering a building the wire can change to NM) (Cannot use UF wire in conduit)
e
. Conduit
i
. PVC – All PVC conduit* must be buried at least 18” deep
ii
. Metal – All Rigid Metal Conduit* must be at least 6” deep
* Wires used in conduit must be single strand wires (ex: THHN, XHHN, etc) NO UF CABLE

2) Convenience Receptacle (Outlet) and Wiring Method

a. At least one (1) convenience receptacle must be located not closer than 6’ but not further than 20’ from the inside pool wall (Can be existing and/or wired with any approved wiring method)
b. Convenience receptacle must be GFCI protected.
c. Must have a weatherproof cover where exposed to the weather (In-use type cover required on used, unattended, receptacles in wet locations)
d. Must be separate from the pool pump receptacle wiring.
e. Wiring
i. UF cable if buried must be at least 24” deep
ii. PVC – All PVC condui* must be buried at least 18” deep
iii
. Metal – All Rigid Metal Conduit* must be at least 6” deep
* Wires used in conduit must be single strand wires (ex: THWN, XHHN, etc) NO UF CABLE


3) Bonding The Pool

a. All metal parts must be bonded together using a #8 (or larger) solid copper wire. (motor, ladder, lights, etc)
b. Must use non-corrosive clamps.
c. A minimum of nine (9) square inches of metal must be in the water to bond the water
d. Recommend bonding in two (2) spots going ½ way around the pool.
e. Equipotential Bonding is required on all pools with conductive shells. A #8 (or larger) solid copper wire.

4) Other

a.
Building Permits are required. Secure a Building Permit from your municipality prior to beginning work
b. Pool Alarms (Check with your local Building Department for additional information)
c. Pool Pump Timers (Check with your local Building Department for additional information)

Check with your local building department for any additional requirements and/or restrictions prior to beginning work

 


PRINTABLE VERSION

 


Should you have questions, problems or
suggestions regarding our web site please contact our WebMaster

[ ABOUT GHI HOME ][ HOME INSPECTION ][ INSPECTION FEES ][ SET AN APPOINTMENT] [RADON TESTING ][ PEST INSPECTIONS ][ CUSTOMER TESTIMONIALS ][ FEATURE TOPICS] [ BROKERS AND REAL ESTATE AGENTS ][SCHEDULE APPOINTMENT ON-LINE][CONTACT US ]

Gunther Home Inspections, Inc.
Voice 585-349-3900 - Fax 585-349-3834
2767 Dewey Avenue - Rochester, NY 14616 - www.InspectNY.com
NYS# 16000005972
 © 1998-2012 Gunther Home Inspections, Incorporated